Zero CO2
+34 91 802 16 49 info@masterbattery.es

Beta 100K-5G

Beta 100K-5G
Beta 100K-5G

Beta 100K-5G Series

Efficient
10 MPPTs, max. efficiency 98.7%.
> 150% DC/AC ratio.
High power tracking density 90MPPT/MW. Compatible with bifacial modules.

Smart
Night SVG function.
Intelligent string monitoring. Smart I-V curve scan. Remote firmware upgrade with simple operation.

Safe
AFCI protection, proactively reduces fire risk.
Built-in PID recovery for better module performance (optional).
Type I SPD for AC (optional).
Overvoltage load reduction and leakage current suppression technology, low failure rate.
Globally recognised branded componentry for longer life.

Economic
Power line communication (PLC) (optional).
Support "Y" type connection in DC side.
Supports aluminium wire access to reduce cost.

Specifications

MODEL Beta 100K-5G
INPUT DC
Maximum Input Voltage (V) 1100
Rated Voltage (V) 600
Start-up Voltage (V) 195
MPPT Voltage Range (V) 180-1000
Maximum Input Current (A) 10*26
Maximum Short Circuit Current (A) 10*40
MPPT Number/Max. Input Strings Number 10/20
OUTPUT AC
Rated Output Power (kW) 100
Maximum Apparent Output Power (kVA) 100
Maximum Output Power (kW) 110
Rated Grid Voltage (V) 3/N/PE, 220/380, 230/400
Rated Grid Frequency (Hz) 50 / 60
Rated Grid Output Current (A) 152.0/144.3
Maximum Output Current (A) 167.1
Power Factor > 0.99 (0.8 leading - 0.8 lagging)
THDi < 3%
EFFICIENCY
Maximum Efficiency 98.7%
EU Efficiency 98.3%
PROTECTION
DC Reverse-Polarity Protection Yes
Short Circuit Protection Yes
Output Over Current Protection Yes
Surge Protection Type II/AC Type II (AC Type I optional)
Grid Monitoring Yes
Anti-Islanding Protection Yes
Strings Monitoring Yes
I/V Curve Scanning Yes
Integrated PID Recovery Optional
Integrated AFCI (DC arc-fault circuit protection) Yes
Integrated DC Switch Yes
Integrated AC Switch Optional
GENERAL DATA
Dimensions (W*H*D) (mm) 1065*567*344.5
Weight (kg) 84
Topology Transformerless
Self Consumption (Night) < 2W
Operating Ambient Temperature Range -25 ~ 60°C
Relative Humidity 0 ~ 100%
Ingress Protection IP66
Cooling Concept Intelligent redundant fan-cooling
Maximum Operation Altitude 4000 m
Grid Connection Standard VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1, UTE C15-712-1, NRS 097-1-2, G98, G99, EN 50549-1/-2, RD 1699, UNE 206006, UNE 206007-1, IEC61727, DEWA
Safety/EMC Standard IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4
FEATURES
DC Connection MC4 connector
AC Connection OT terminal (max. 185 mm²)
Display LCD
Communication RS-485, Optional: Wi-Fi, GPRS, PLC

Product specifications are subject to change without further notice.