DATA SHEET |
|
Maximum PV Input Power |
45 KW |
Rated Output Power |
30 KW |
Maximum Charging Power |
30 KW |
|
GRID-TIE OPERATION |
|
|
PV
INPUT
(DC) |
Nominal DC Voltage |
720 VDC |
Maximum DC Voltage |
950 VDC |
Start-up Voltage / Initial Feeding Voltage |
500 VDC / 550 VDC |
MPP Voltage Range |
500 ~ 900 VDC |
Full power MPP Voltage Range |
625 ~ 900 VDC |
Number of MPP Trackers |
1 |
Maximum Input Current |
72 A |
|
GRID/UTILITY
OUTPUT
(AC) |
Nominal Output Voltage |
230 VAC* (P-N) / 400 VAC (P-P) |
Output Voltage Range |
184 - 265 VAC per phase |
Output Frequency Range |
47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz |
Nominal Output Current |
43.5 A per phase |
Power Factor |
> 0.99 |
|
EFFICIENCY |
Maximum Conversion Efficiency (DC/AC) |
95% |
|
OFF-GRID OPERATION |
|
AC
INPUT |
AC Start-up Voltage |
150 - 170 VAC per phase |
Auto Restart Voltage |
180 VAC per phase |
Acceptable Input Voltage Range |
170 - 280 VAC per phase |
Maximum AC Input Current |
65 A per phase |
|
|
PV
INPUT
(DC) |
Maximum DC Power |
45 KW |
Maximum DC Voltage |
950 VDC |
MPP Voltage Range |
500 ~ 900 VDC |
Number of MPP Trackers |
1 |
Maximum Input Current |
72 A |
|
BATTERY
MODE
OUTPUT
(AC)
|
Nominal Output Voltage |
230 VAC (P-N) / 400 VAC (P-P) |
Output Frequency |
50 / 60 Hz (auto sensing) |
Output Waveform |
Pure sine wave |
Efficiency (DC to AC) |
> 91% |
|
|
HYBRID OPERATION |
|
PV
INPUT
(DC) |
Maximum DC Power |
45 KW |
Nominal DC Voltage |
720 VDC |
Maximum DC Voltage |
950 VDC |
Start-up Voltage / Initial Feeding Voltage |
500 VDC / 550 VDC |
MPP Voltage Range |
500 ~ 900 VDC |
Number of MPP Trackers |
1 |
Maximum Input Current |
72 A |
|
GRID/UTILITY
OUTPUT
(AC) |
Nominal Output Voltage |
230 VAC (P-N) / 400 VAC (P-P) |
Output Voltage Range |
184 - 265 VAC per phase |
Output Frequency Range |
47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz |
Nominal Output Current |
43.5 A per phase |
Power Factor |
> 0.99 |
|
AC
INPUT |
AC Start-up Voltage |
150 - 170 VAC per phase |
Auto Restart Voltage |
180 VAC per phase |
Acceptable Input Voltage Range |
170 - 280 VAC per phase |
Maximum AC Input Current |
43.5 A per phase |
|
|
BATTERY
MODE
OUTPUT
(AC) |
Nominal Output Voltage |
230 VAC (P-N) / 400 VAC (P-P) |
Output Frequency |
50 / 60 Hz (auto sensing) |
Output Waveform |
Pure sine wave |
Efficiency (DC to AC) |
> 91% |
|
|
BATTERY
&
CHARGER |
Nominal Battery Voltage |
348 ~ 384 VDC (adjustable) |
Maximum Charging Current |
80 A |
|
GENERAL |
|
|
PHYSICAL |
Dimension, D x W x H (mm) |
745 x 600 x 1140 |
Net Weight (kgs) |
368 |
|
|
INTERFACE |
Communication Port |
RS - 232 / USB |
Intelligent Slot |
Optional SNMP, GRPS, WIFI, Modbus cards available |
|
|
ENVIRONMENT |
Humidity |
0 ~ 90% RH (No condensing) |
Operating Temperature |
-10°C to 55°C |
Altitude |